MAIN FEATURES | |
---|---|
Capacity | 30KVA / 24kW |
Model | SAARLAND-LX3130 |
Brand | G-Mac |
Brand Origin | Germany |
Technology | Transformer Based Industrial UPS |
INPUT | |
Phase | 3:1 |
Nominal Voltage | 380/Vac (1±20%), (3Ph+N+PE) |
Frequency Range | 50/60Hz(1±5Hz) |
Power Factor | >0.97(with filter) |
Max. Input Current(A) | 68 |
OUTPUT | |
Output Voltage | 220Vac (1±1%) |
Output Frequency | 50/60Hz (1±1%) |
Current crest Ratio | 3:1(Max) |
Efficiency | Online:90% |
THDv | <1.5% with linear load |
BATTERY | |
Battery Voltage | 384Vdc |
Charging Current | 6A/12A(Optional) |
SYSTEM FEATURES | |
Transfer Time | Utility ↔ Battery: Oms |
Overload | Load≤125%/ 1min; ≤150% /200ms, to Bypass |
Communication Interface | RS232, SNMP (optional), Dry contact, RS485 |
ENVIRONMENT | |
Operating Temperature | 0~40°C |
Storage Temperature | -25℃~55℃ |
Humidity Range | 0~95% (Non-condensing) |
Altitude | <1500m |
Noise level<55dB | <55dB |
STANDARDS | |
Safety | IEC/EN62040-1;IEC/EN60950-1 |
EMC | EC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |
SAARLAND-LX31 series UPS is a three-phase in and one phase out online transformer-based UPS, with parallel function, flexibly response to the expansion and redundancy requirement of customer, widely used in finance system, telecom system, electric power system, working station, etc.
General Features
● True online double conversion design
● Build-in input and output transformer with strong galvanic isolation
● Wide input range, avoid frequently transfer to battery mode, prolong the battery lifetime
● With parallel function, flexibly response to the expansion and redundancy requirement
● Intelligent battery management technology, fully protect the battery
● Battery cold start function
● Comprehensive and reliable protection